Part of Rockwell Automation 's efforts to improve security practices, including tamper prevention and detection.

You saved a project using v20.01 and now you have v20.12, but the software complains. Solution: Open the project in RSLogix 5000 v20.12. Go to Logic > Controller Properties > General . Change the "Revision" from 20.1 to 20.12. If the project is read-only, export the logic as a .L5K file, edit the revision number in Notepad, and re-import. rslogix 5000 firmware 20.12

The controller is at v20.12, but communications fail with 1756-ENBT or EN2T cards. Solution: v20.12 requires matching firmware revisions on communication modules. Ensure your ENBT card is at least v5.2. Flash all backplane modules to their latest compatible firmware. Part of Rockwell Automation 's efforts to improve